![]() Cryogenic Liquid Pump InstallationSome problems to avoidBy Denis O. DePierro |
||||||||
|
Reliable, trouble-free pump operation is the key to low-cost cryogenic liquid pumping. When installing either reciprocating or centrifugal cryogenic liquid pumps, careful up-front planning can mean the difference between long-term reliability or excessive maintenance and consequent downtime. This article describes the general principle issues to be addressed before and during installation of reciprocating and centrifugal pumps. Most topics apply to both types of installations. However, several additional considerations apply only to centrifugal pumps. The mounting procedures and suction and discharge piping considerations described in the following paragraphs apply equally to reciprocating and centrifugal pumps. Mounting to Pad
When planning the installation, take into account the location of the pump with respect to the tank and the process so as to minimize piping runs. For the suction connection, the pump should be placed at a location that limits the piping run to less than 5 feet (1.5 meters) from the tank. All pipes in the system should have a pressure rating above system design pressure. Use as few elbows as possible to minimize liquid turbulence in the line and lessen pressure drop. The suction line should have a slight and continuously downward slope to aid in maintaining liquid flow into the suction fitting. At no point should the line rise and then drop (creating a gas trap). A gate or ball valve, rather than a globe valve, should be used in the suction line. An inlet strainer is needed in suction piping except for most ACD reciprocating pumps, which have a strainer built into the suction fitting. A differential pressure gauge should be used across the suction strainer. Avoid the use of suction piping having a different diameter from the pump inlet fitting. If the diameter is too large, product flows too slowly. This permits excessive heat leak into the fluid, which may cause the pump to cavitate. Conversely, small diameter piping increases pressure losses, which reduces NPSH and thereby may also cause cavitation.
For reciprocating pumps, connect the suction fitting to a 6 to 8-inch long (15 to 20 cm) (maximum) flexline to compensate for expansion and contraction. Flexlines should not be used to compensate for misalignment or poor piping installations. Also, do not use full-length flexlines, as they add considerably to pressure drop and heat leak. If the suction piping is relatively long, insulation should be considered. Vacuum-jacketed insulation is preferred because other conventional types of insulation may accumulate moisture, resulting in loss of insulation effectiveness and possibly causing cavitation due to heat leak. For operating cycles that are infrequent and of short duration, conventional insulation might be detrimental because the mass of insulation must be cooled down each time the pump is operated. Whenever possible, pump suction piping should be separate from other liquid lines. If other pipes must be connected to the pump's suction pipe, a valve must be placed directly adjacent to the connection to prevent a dead-leg. A dead-leg is a void where liquid can vaporize, which adds heat to the fluid and could cause bubbles to flow into the pump and possibly cause cavitation. Gas Phase Return Piping For centrifugal pumps, a gas phase recirculation line is needed on the discharge side for pump cool down and startup. A globe valve should be installed in this line to allow throttling during startup. A discharge control valve, downstream of the recirculation valve, must be located as close as possible to the pump to control the flow to be on the pump's curve. Allowing the pump to start against no restriction, or to fill a large volume before control is established, will cause severe cavitation and likely the inability to catch prime.
A relief valve must be used to prevent over-pressure from vaporized trapped-liquid when the suction and gas-phase return valves are simultaneously closed. When a relief valve is installed in the gas-phase return line, it is not necessary to install a second relief valve in the suction line. Discharge Piping Relief Valves
For unattended operation, fully automated systems are available to control the operation and shut down the pump if a vault occurs, such as cavitation, seal leak, or over-pressurization. The issues discussed provide general guidance for pump installations. However, each installation is unique. Always use sound engineering practices for a pump installation. |
||||||||
|
||||||||